BATTERY SIZING

Let us have total load of 16 kW with 0.8 pf, which needs to be supported by battery backup for at least 1 hr, when the grid fails. Before choosing the battery with respect to cost or brand, there are many questions to be answered

  • Which type of battery?
  • C-rating of the battery?
  • What is the UPS Voltage window?
  • UPS rating?
  • No: of Batteries (blocs) required?
  • How many cells per bloc?
  • How many blocs in series?
  • How many blocs in string (parallel)?
  • What is the End Cell Voltage (ECV)?
  • What is the Temperature correction factor with respect to the ambient
    temperature?
  • What is the Discharge power per cell with respect to ECV and backup time?
  • What is the Discharge current per cell with respect to ECV and backup time?
  • What is the ageing factor considering end of life criterion?
  • What is the K factor?
  • For space constraints, bloc dimensions?
  • No: of blocs per rack?

Battery sizing calculation differs with respect to application as well

  • UPS
  • Telecommunications
  • Solar Photovoltaic

REFERENCE STANDARDS / DOCUMENTS:

  • IEEE 1184-2006 – Guide for Batteries for Uninterruptible Power Supply Systems
  • Highlighted values are taken from reputed vendor catalogue available on the internet for calculation purpose.

UPS BATTERY SIZING CALCULATION:

Battery load of UPS should be calculated by considering the following 4 margin factors as shown below

Actual load / Inverter Efficiency = Nominal battery load
Temperature correction factor x Design Margin x Aging Margin x Overloading factor = Battery load

Selected Battery type Sealed Maintanence Free VRLA.

UPS Output rating = 20 kVA
Output Power Factor = 0.8
Actual Load = 16 kW
Inverter Efficiency (EFF) = 94%
Nominal Battery load = 17.02 kW

Temperature correction factor for 25°C = 1.00
Design Margin = 1.10
Aging Margin = 1.25
Overloading Factor = 1.10

Calculated Battery load = 25.74 kW

End Cell Voltage (ECV) should be maintained
well within the voltage window of the UPS.

Nominal DC voltage = 400 Vdc
Maximum Rectifier equalizing voltage = 432 Vdc
Inverter low voltage cut-off = 290 Vdc
Voltage drop of DC cables is assumed = 2 Vdc
Minimum required UPS voltage = 292 Vdc

Boost charge = 2.4 Vdc
Equalizing Cell Voltage = 2.25 Vdc
End cell Voltage (ECV) Selected = 1.75 V/Cell
Nominal Cell Voltage = 2 V/Cell

Battery Model Selected = LX-12 150

Total No.of cell x ECV > Cut-off voltage
Let us assume 1 hr be the required backup time

Minimum number of cells required = 166.86 Nos.
Total number of cells selected = 180.00 Nos.
Backup time = 60 mins.
Required cell discharge for 1hrs in Watts = 143.03 W/cell
Available cell discharge for 1hrs in Watts = 203 W/cell
No.of strings = 1 Nos.
Number of cells per bloc = 6 Nos.

As the selected battery bloc is 12V
(Total No.of 2V cells) / 6 = No.of Blocs
180/6 = 30

Number of blocs required = 30 Nos.

UPS datasheet:

Thinesh babu V

– Power System Designer