Short Circuit Calculation
- In this model, grid is modelled with short circuit current of 40kA and X/R ratio of 14, two winding transformer rating of 100 MVA, 220/33kV, %Z is 8.35 and X/R is 13.
- Fault is created at bus 2, the calculations for symmetrical RMS current is made below.
Impedance Correction Factor:
Transformer Impedance:
Grid Impedance:
Three Phase Fault:
Manual Calculations for Unsymmetrical Fault Current
- The same model is considered here, for calculation of unsymmetrical fault, the SLG fault is considered.
- The fault is created at bus 2 under no load condition i.e. Current before fault occurrence is zero.
- Due to unbalance nature in power system due to unsymmetrical fault, there will be positive, negative and zero sequence currents.
- Fault Impedance is considered to be zero.
Positive Sequence network (Z1):
Negative Sequence Network (Z2):
Zero sequence Network (Z0):
Single Line to Ground Fault:
The fault current for SLG fault is
Line to Line Fault:
The fault current for SLG fault is
Double Line to Ground Fault:
The fault current for DLG fault is